Description
Product Description
Hikvision DS-UPS06K-R/TJL/IEC
The output offers a pure sine wave (3:
Specification Hikvision DS-UPS06K-R/TJL/IEC
| Power | UPS Capacity | 6000 VA / 6000 W |
| Input | Nominal Voltage | 208/220/230/240Vac |
| Phase | Single Phase | |
| Input Voltage Range | 110~300Vac (110~300Vac@50% load/176~300Vac@100% load) | |
| Input Frequency | 40~70Hz (50/60Hz Auto-Sensing) | |
| Power factor | ≥0.99 | |
| Output | Output Voltage | 208/220/230/240Vac |
| Crest factor | 3:1 | |
| Power factor | 1 | |
| Output Sockets | IEC version: Connecting terminal +IEC socket / US version: Connecting terminal+US socket panel | |
| Output Frequency | Online mode:±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional) Battery mode: (50/60±0.1%)Hz | |
| Harmonic distortion (THDv) | ≤1% Linear load / ≤3% Non linear load | |
| Transfer Time | AC mode to Bat.mode: 0ms Inverter to Bypass: 0ms | |
| Output Waveform | Pure Sinewave | |
| Battery | Battery Type | Valve Regulated Lead Acid (VRLA) |
| DC System Voltage (VDC) | 192/240Vdc (Settable) | |
| Charging Current (Max.) | 12A | |
| Expandable Runtime | Yes, External battery pack: DS-UPSB09192A-R/TJ, or DS-UPSB09240A-R/TJ | |
| Typical Backup Time | View Runtime Graph | |
| Indicator | Alarm | Battery mode/Battery low voltage/Overload/Fault |
| LCD display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time | |
| Efficiency | AC Mode | Up to 95% |
| Battery Mode | Up to 93% | |
| Environment | Operating Temperature | 0℃~40℃ |
| Storage Temperature | -25℃~55℃ | |
| Humidity Range | 0~95% (Non - condensing) | |
| Altitude | 0~3000m (1000~3000m derating required) | |
| Noise Level | ≤50dB | |
| Physical | Dimension W x D x H (mm) | 440×621.5×86.5 |
| Net weight (kg) | 15.5 | |
| Standards | Safety | CE-LVD IEC/EN 62040-1, IEC/EN 62477-1 |
| EMC | CE-EMC IEC/EN 62040-2 (IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, IEC61000-2-2) |
*We have done our best to provide an accurate description and specifications. Please note that these were created and translated automatically using manufacturer data. Colors and appearance may look different depending on your monitor settings. Before buying, please check the product sheet from the manufacturer for official information. The “Specification” section may refer to different variants of the same device (depending on the exact model name/identifier). If anything is unclear or inconsistent, please contact the seller before purchase. If warranty information is provided, it refers to the manufacturer’s warranty unless stated otherwise. Product images may show multiple color variants. If the model name does not include a color designation, it typically refers to the default version (e.g., for cameras: white). Other variants are indicated in the product name, such as “Black” or “BLK”.