Description
Power supply | 230 V AC |
Power supply output | 3.2 A / 27.6 V DC - for continuous operation – Imax a 5 A / 27.6 V DC - for intermittent operation – Imax b (5min) |
Compliant with standards | Fire protection standard EN54-4Smoke extraction and ventilation standard EN12101-10Certificate of constancy of performance CNBOP-PIB No 1438-CPR-0630 |
Battery charging current | 1.8A |
Battery | 2 x 17÷45Ahno space for battery |
Current consumption by PSU systems | 55mA max. |
Efficiency | 87% |
Dimensions | 204 x 141 x 52 [+/-2 mm] |
Protections | SCP, OLP, OVP, UVP |
Technical outputs relay type | EPS – AC power failureALARM – collective failure |
Technical input | EXTi – external failure |
Warranty | 3 years from production date |
Notes | - built-in power supply module - DIN rail mounted, EN54M-DIN1 bracket required - To be able to install module of PSU in fire alarm system, it must be placed in enclosure of appropriate design and make complementary examinations to achieve certificate PN-EN54-4+A1+A2 or PN-EN12101-10+AC |